1. Morocco
  2. Tous les produits 3M
  3. Electrical
  4. Power Cable Connectors
  5. Power Cable Terminations
  6. 3M™ Cold Shrink QT-II Termination Kit, Termination 92-EB 62-3, Application up to 12KV

3M™ Cold Shrink QT-II Termination Kit, Termination 92-EB 62-3, Application up to 12KV

  • 3M ID 7000035264
Voltage 6/10 kV
Insulation Outer Diameter (Metric) 22.1 Millimetre
Number of Conductors 3
Breakout Boot Yes
Cable Shielding Wire Shield
Number of Skirts 0

Designed for 12 kV Umax voltage class, three-core, polymeric power cable systems

Suitable for copper wire or tape screened cables, with or without armour

Indoor application range 70-95 mm²

View more details
Frequently viewed resources
PDF (1) Copy 26Tech Data Sheet (PDF, 69KB)

Details

Highlights
  • Designed for 12 kV Umax voltage class, three-core, polymeric power cable systems
  • Suitable for copper wire or tape screened cables, with or without armour
  • Indoor application range 70-95 mm²
  • Fast and easy installation at temperatures ranging from -20 °C to +50 °C
  • No heat/flame or tools are required for installation
  • Kit of 3 phases

3M™ Cold Shrink Termination QTII 92-EB62-3 is our kit containing 3M™ Cold Shrink QTII silicone termination body with integrated stress control device, silicone elastomeric insulation, armour continuity components, rejacketing tubes, three-core Cold Shrink breakout boots, silicone tape and detailed instructions for installing.

For 12 kV Umax voltage class, three-core, polymeric power cable systems, use 3M™ Cold Shrink Termination QTII 92-EB62-3. Our termination kit is designed for power cables with copper wire, tape screen or armour according to HD 620 (IEC 60502), and has a 70-95 mm² indoor application range. It features a prefabricated Cold Shrink termination body which allows fast and easy installation on a wide range of cable types and sizes, at temperatures ranging from -20 °C to +50 °C. The constant force springs offer a solderless earth connection and includes silicone tape for moisture sealing. No heat/flame or tools are required for Cold Shrink installation. 3M™ Cold Shrink Termination QTII 92-EB62-3 meets and exceeds the requirements of European Standard CENELEC HD 629.1 and IEC 60502-4.

Typical Properties

Resources